Zhejiang Jiuguang Electric Power Technology Co., Ltd. located in the famous scenic spot south of the country, close to Ningbo-Taizhou-Wenzhou Expressway, and 104 National Road phase, superior geographical environment, transportation convenience.Our main production isolating switches, vacuum circuit breakers, load switch, operating mechanism, such as high-voltage electrical products, domestic products have reached the advanced level, and passed ISO9001: 2000 international quality system certification. National high-voltage electrical Quality Supervision and Inspection Center. The factory to innovation, quality win for the purpose. Has a number of highly qualified technical staff, complete production equipment and advanced testing equipment, to provide customers with high-quality products and quality service.
Add:Niqian Industrial Zone, Liushi Town, Yueqing City, Zhejiang Province
Fax:086-0577-62601830
Serverphone:086-400-8070-830
Tel:086-0577-62602830
Photo:086-13736777007
E-mail:qydl66@163.com
Description:
FZW33 12KV/24KV Outdoor AC vacuum disconnect load breaker is a new product adopts domestic existing mature load breaker switch production experience and overseas advanced technology to design and manufacture. The load breaker is composed of disconnect blade, vacuum interrupter and operation mechanism. vacuum extinguishing arc, there are merits as strong extinguishing arc ability, reliable performance, long lifetime, small volume, no explosive danger and no pollution to environment.
It accords with the standards of IEC62271-112 & GB/T3814:3.6~41.5kV High voltage switches, IEC61694 & GB/T11122: High voltage switch apparatus and control apparatus.
Techincal data:
N1.
Test Item
Unit
Data
1
Rated voltage
kV
12
24
2
Rated current
A
411/631
411/631
3
Rated frequency
Hz
51/61
51/61
4
Rated short-time withstand current
kA
21
21
5
Rated short-circuit duration
s
4
4
6
Rated active load breaking current
A
411/631
411/631
7
Rated loop breaking current
A
411/631
411/631
8
Rated cable charging current
A
12
12
9
5% rated active load breaking current
A
31.5
31.5
11
Rated short-circuit making current
kA
51
51
11
Main loop resistance
μΩ
≤111
≤111
12
power frequency withstand voltage against the earth, between phases
kV rms
41
65
13
power frequency withstand voltage against the isolating distance
kV rms
48
79
14
Lightning impulse withstand voltage against the earth, between phases (peak)
kV
75
125
15
Lightning impulse withstand voltage against the air gap(peak)
kV
85
145
16
Mechanical life
Times
11111
11111
17
Three phase closing asynchronous
ms
≤5
≤5
18
Main contact blade pressure
N
521
521
19
Distance between electric parts and phase to earth
mm
≧311
≧611
21
Rated operating force
N
≤311
≤311