Zhejiang Jiuguang Electric Power Technology Co., Ltd. located in the famous scenic spot south of the country, close to Ningbo-Taizhou-Wenzhou Expressway, and 104 National Road phase, superior geographical environment, transportation convenience.Our main production isolating switches, vacuum circuit breakers, load switch, operating mechanism, such as high-voltage electrical products, domestic products have reached the advanced level, and passed ISO9001: 2000 international quality system certification. National high-voltage electrical Quality Supervision and Inspection Center. The factory to innovation, quality win for the purpose. Has a number of highly qualified technical staff, complete production equipment and advanced testing equipment, to provide customers with high-quality products and quality service.
Add:Niqian Industrial Zone, Liushi Town, Yueqing City, Zhejiang Province
Fax:086-0577-62601830
Serverphone:086-400-8070-830
Tel:086-0577-62602830
Photo:086-13736777007
E-mail:qydl66@163.com
  • Desciption
Description:
FZW33 12KV/24KV Outdoor AC vacuum disconnect load breaker is a new product adopts domestic existing mature load breaker switch production experience and overseas advanced technology to design and manufacture. The load breaker is composed of disconnect blade, vacuum interrupter and operation mechanism. vacuum extinguishing arc, there are merits as strong extinguishing arc ability, reliable performance, long lifetime, small volume, no explosive danger and no pollution to environment.
It accords with the standards of IEC62271-112 & GB/T3814:3.6~41.5kV High voltage switches, IEC61694 & GB/T11122: High voltage switch apparatus and control apparatus.
Techincal data:
N1. Test Item Unit Data
1 Rated voltage kV 12 24
2 Rated current A 411/631 411/631
3 Rated frequency Hz 51/61 51/61
4 Rated short-time withstand current kA 21 21
5 Rated short-circuit duration s 4 4
6 Rated active load breaking current A 411/631 411/631
7 Rated loop breaking current A 411/631 411/631
8 Rated cable charging current A 12 12
9 5% rated active load breaking current A 31.5 31.5
11 Rated short-circuit making current kA 51 51
11 Main loop resistance μΩ ≤111 ≤111
12 power frequency withstand voltage against the earth, between phases kV rms 41 65
13 power frequency withstand voltage against the isolating distance kV rms 48 79
14 Lightning impulse withstand voltage against the earth, between phases (peak) kV 75 125
15 Lightning impulse withstand voltage against the air gap(peak) kV 85 145
16 Mechanical life Times 11111 11111
17 Three phase closing asynchronous ms ≤5 ≤5
18 Main contact blade pressure N 521 521
19 Distance between electric parts and phase to earth mm ≧311 ≧611
21 Rated operating force N ≤311 ≤311